logo_3.jpg (3319 bytes)

welcome1.gif (5069 bytes)


tel.: +421 41 7234 862

eliss@eliss.sk

slovak

english

______________________________________________________________________


Products

 

NEUPOS-01.1

 

MODUL OF FAULT SIGNALLING

Functions:

  • following of 10 faults
  • sensing and processing of faults in I. a II. level per one module
  • optional ratio between faults of I. and II. level
  • recognition of first faults and following non-confirm faults
  • recognition of the first and (non)confirm faults
  • separate relay outputs for I. level faults
  • separate relay outputs for II. level faults
  • separate relay output for acoustic signalling of arisen faults
  • separate relay output for modem
  • 2 reserved inputs
  • data storing during power failure
  • LONWORKS® communication, and/or with superior system

HW description:

  • 10 optocouplling digital inputs (I1 ÷ I10) for following of 10 faults according jumpers for configuration of I. and II. level faults
  • 1 optocouplling digital input (P) for faults confirmation
  • 1 optocouplling digital input (S) for light and acoustic signal check
  • 10 optocouplling digital transistor outputs (O1 ÷ O10) for light indication, which signal faults for each input
  • 2 optocouplling digital transistor outputs for free use
  • 4 relay output for signalling of:
    • I. level faults
    • II. level faults
    • acoustic alarm
    • modem plugging
  • 2 jumpers (P1, P2) for option of amount of I. and II. level faults
  • 2 jumpers (P3, P4) reserved
  • micro-button (MT1) for LONWORKS® (SERVICE PIN)
  • micro-button (MT2) for external reset of module
  • standard communication LONWORKS® interface FTT10
  • compact construction in mounting frame to DIN rail

Description:

Fault signalling module - based on LONWORKS® - senses, processes and indicates summary 10 faults in I. and II. level (rate of both is optional according jumpers) with the time recognition of the first and followed faults. There are possibility to plug check and confirmation pushbuttons, acoustic alarm and telephone modem, too. LONWORKS® CPU module is equipped by FTT10.

NEUPOS 01 is proposed for mounting to the distributors and the technological equipments. Monitoring of the heating houses without operator is the typical use of NEUPOS 01.

Application SW is possible to accommodate to customer needs.

Technical data:

Parameters

Value

Units

  Power supply

24 ± 20%

V DC

  Current consumption (without input load)

< 100

mA

  Summary number of fault inputs

10

-

  Number of auxiliary inputs

2

-

  Type of inputs

24/5

V/mA

  Input level - log. 0

< 3

V

  Input level - log. 1

> 12

V

  Sample trigger for fault occurrence

> 20

ms

  Number of outputs

10

-

  Type of digital outputs

24/100

V/mA

  Number of auxiliary transistor outputs

2

-

  Type of auxiliary transistor outputs

24/100

V/mA

  Number of auxiliary relay outputs

4

-

  Type of auxiliary relay outputs

250/8

24/8

V/A AC

V/A DC

  Number of config. jumpers

2

-

  Number of auxiliary jumpers

2

-

  Input protection - glass fuse

F250/1,4

V/A

  CPU board protection - glass fuse

F250/0,1

V/A

  Protection class

IP00

-

  Dimension

165 x 125 x 48

mm

  Mounting on rail

DIN 35

-



Back